Multi, Abdul Leak Current Monitoring System On The Ground Cables Medium Voltage Transformer 150/20 kV. [Teaching Resource]
Text
Leak_Current_Monitoring_System_On_The_Ground_Cable.pdf Download (500kB) |
Abstract
Abstract. On January, 2017 there had been fault trip at PMT 150/20 kV transformer in Jatirangon substation. For fault detection, that rele differential phase T and REF 20 kV have worked to detect this fault. The resulted impact of this fault is Power outage in feeder a 1350 A, 35 MW and 5 Mvar. The cause of this fault is the occurrence of breakdown on ground cables 20kV T-phase-core 1. This results in a short circuit to the ground so that the differential protection relay and REF 20kV work because the relay detects a fault in the ptotection zone. The result of this research is the design of an early detection monitoring tool. This tool is used to determine the amount of leakage current on the ground cable in order to minimize the occurrence of interference that causes the occurrence of electrical power outage. The result of the leakage current monitor on the ground phase cable T obtained a current of 0.6A with temperature 35 oC. With thermal failure calculation method for leakage current obtained result of 0,56180A with temperature 35 oC. Comparison of the calculation with the measurement of leakage current on the ground cable T phase is obtained at 6.36%.
Item Type: | Teaching Resource |
---|---|
Subjects: | L Education > L Education (General) |
Divisions: | Faculty of Engineering, Science and Mathematics > School of Electronics and Computer Science |
Depositing User: | ABDUL MULTI ISTN |
Date Deposited: | 07 Mar 2022 08:50 |
Last Modified: | 07 Mar 2022 08:50 |
URI: | http://repository.istn.ac.id/id/eprint/3262 |
Actions (login required)
View Item |